Anti-freezing Solutions for Closed Circuit Cooling Towers
Drainage Method
Completely drain all water from coils/pipes after shutdown
Recommended to use compressed air for residual water removal
Best for: Equipment with long-term winter shutdown
Electric Tracing System
Install self-regulating heating cables on makeup water pipes/spray pipes
Maintain water temperature >5℃ (Power consumption:15-30W/m)
Must be used with insulation layers
Glycol Solution
Recommend industrial-grade ethylene glycol
Concentration guidelines:
North China:20%-25%
Northeast China:30%-40%
Annual pH test required (optimal range:7.5-9.0)
Smart Control Strategies
Install low-temperature sensors (alarm trigger ≤3℃)
Set circulating pump intermittent operation (suggested 30min/cycle)
Interlock control for electric heaters